Light Pole Anchor Bolt Replacement

Reuse an existing concrete footing with a properly engineered anchor bolt solution.

Damaged, broken, missing, or misaligned light pole anchor bolts do not always require a new concrete footing. Light Pole Systems offers Anchor Bolt Adapter and drill-and-epoxy solutions for qualifying applications.

Common Light Pole Anchor Bolt Problems

Light pole anchor bolt problems often appear when replacing an existing pole, installing a different pole on an existing footing, or dealing with damaged hardware.

Misaligned light pole anchor bolt pattern on existing concrete footing

Misaligned bolt pattern

Rusted and deteriorated light pole anchor bolts on concrete footing

Rusted or deteriorated bolts

Bent light pole anchor bolt on existing concrete footing

Bent anchor bolts

Broken-off light pole anchor bolts on existing concrete footing

Broken-off bolts

Missing light pole anchor bolts on existing concrete footing

Missing bolts

Broken-off light pole anchor bolts on existing concrete footing

No usable anchor bolts

Replacement light pole base plate with a different bolt circle than existing concrete anchor bolts

Different bolt circle

Close-up of a replacement light pole base plate with a different bolt circle than the existing anchor bolt pattern on the concrete footing, illustrating a common mismatch that may require an Anchor Bolt Adapter or drill-and-epoxy retrofit solution.

New anchor locations needed

Which Light Pole Anchor Bolt Solution Is Right for Your Project?

Not every light pole anchor bolt problem requires the same repair. The right solution depends on the condition of the existing anchor bolts, the concrete footing, the required bolt circle, the replacement pole specifications, and the project’s EPA and structural load requirements.

Light Pole Systems recommends evaluating the available options in this order.

1

Anchor Bolt Adapter

Use first when the existing anchor bolts are still usable but the replacement pole has a different bolt pattern.

Consider an adapter when:

  • Existing anchor bolts are still usable
  • Bolt-circle adjustment is within the adapter range
  • EPA load is within the adapter rating
  • Avoiding new drilling is preferred
2

AT.75 or AT1 Drill-and-Epoxy Anchors

Use when existing anchor bolts cannot be reused or the required adjustment exceeds the Anchor Bolt Adapter limits.

Consider a drill-and-epoxy system when:

  • Bolts are rusted, bent, broken, or missing
  • No usable anchor bolts remain
  • New anchor locations are needed
  • Adjustment exceeds the adapter range
3

Replace the Concrete Footing

Use when the existing foundation is not suitable for reuse or cannot support the required loads.

Footing replacement may be necessary when:

  • Concrete is cracked or deteriorated
  • Embedment or edge distance is insufficient
  • The footing is undersized
  • Retrofit solutions are not appropriate

Final selection should consider the existing footing, anchor condition, bolt circle, pole specifications, EPA load, and project engineering requirements.

AT.75 & AT1 Drill-and-Epoxy Anchor Bolt Kits

Light Pole Systems offers two drill-and-epoxy retrofit systems for creating new anchor locations in existing concrete footings. The AT.75 uses 3/4-inch all-thread rod, while the AT1 uses 1-inch all-thread rod for larger applications.

AT.75 drill-and-epoxy anchor bolt kit with 3/4-inch all-thread rods, epoxy, nuts and washers

AT.75 Kit

3/4-inch all-thread rod
  • 7/8-inch drill bit
  • 9-inch minimum embedment
  • 7-inch and larger bolt circles
  • Engineering based on 4,000 PSI concrete
AT1 drill-and-epoxy anchor bolt kit with 1-inch all-thread rods, SET-3G epoxy, nuts and washers

AT1 Kit

1-inch all-thread rod
  • 1-1/8-inch drill bit
  • 10-inch minimum embedment
  • 9-inch and larger bolt circles
  • Engineering based on 4,000 PSI concrete

Not sure which kit applies? Compare AT.75 vs. AT1 below.

AT.75 vs AT1: Quick Comparison

Both systems are designed for drill-and-epoxy light pole anchor retrofit applications, but they differ in rod diameter, embedment, and bolt-circle range. Use the light pole manufacturer’s anchor-bolt requirements and project conditions to determine which system applies.

General Selection Guidance

AT.75 is commonly used where 3/4-inch anchor bolts are specified, while AT1 is used where 1-inch anchor bolts are required. Final selection should follow the pole manufacturer’s specifications, bolt circle, footing conditions, EPA load, and engineering requirements.

Bolt-Circle Range & Concrete Requirements

The published AT.75 and AT1 engineering is based on specific bolt-circle ranges, minimum embedment, edge distance, and properly reinforced concrete. Applications outside these published conditions may require additional engineering.

AT.75 Light Pole Bolt-Circle Range

AT.75 Bolt-Circle Range

7" and Larger

Published Tables:

7"

8"

9"

10"

For bolt circles larger than 10″, use the 10″ table as the published reference. Smaller bolt circles may require additional engineering.

AT1 light pole bolt-circle range on concrete footing

AT1 Bolt-Circle Range

9" and larger

Published Tables:

9"

10"

11"

12"

For bolt circles larger than 12″, use the 12″ table as the published reference. Smaller bolt circles may require additional engineering.

Concrete & Installation Requirements

Concrete Strength

4,000 PSI

minimum

Minimum Edge Distance

1-3/4″

AT.75 Embedment

9″ minimum

AT1 Embedment

10″ minimum

Published AT.75 and AT1 load tables presume properly reinforced concrete with a minimum compressive strength of 4,000 PSI.

Applications Outside the Published Requirements

Lower-strength concrete, smaller bolt circles, unusual footing conditions, or project loads outside the published tables may still be possible, but additional engineering may be required. Light Pole Systems can help evaluate these applications.

How the Drill-and-Epoxy Anchor Bolt System Works

The AT.75 and AT1 systems create new light pole anchor locations in an existing concrete footing by drilling new holes, cleaning the holes, installing structural anchoring epoxy, and inserting fully threaded rods to the required embedment depth.

Watch the Light Pole Systems video for a practical overview of the drill-and-epoxy installation process, then use the steps below as a quick reference.

SET-3G Cure Time Depends on Temperature

Based on the Light Pole Systems installation guidance for this system:

70°F and above

24 hours

60°F

48 hours

50°F

72 hours

40°F

192 hours

Cure time is temperature-dependent. Installation should follow the current Simpson Strong-Tie SET-3G requirements and the applicable project engineering before the anchors are loaded.

Installation Overview

1. Layout the New Bolt Pattern

Confirm the replacement light pole manufacturer’s required bolt circle and mark the new anchor locations on the existing concrete footing.

The new anchor locations must also maintain the required edge distance and match the applicable AT.75 or AT1 engineering requirements.

2. Drill the Anchor Holes

Drill each new anchor location to the required diameter and embedment depth for the selected system.

AT.75
  • 3/4-inch all-thread rod
  • 7/8-inch drill bit
  • 9-inch minimum embedment
AT1
  • 1-inch all-thread rod
  • 1-1/8-inch drill bit
  • 10-inch minimum embedment

Both systems use a minimum edge distance of 1-3/4 inches under the published engineering conditions.

3. Clean the Holes

Remove concrete dust and drilling debris from each hole before installing the epoxy.

Proper hole preparation is important for the anchoring epoxy to bond correctly to the concrete and fully threaded rod. Follow the current epoxy manufacturer’s installation procedures for hole cleaning and preparation.

4. Install Epoxy and Fully Threaded Rods

Dispense the specified structural anchoring epoxy into the prepared holes and insert the fully threaded rods to the required embedment depth.

Fully threaded rod is used because the epoxy bonds around the threads along the embedded portion of the rod. A partially threaded rod should not be substituted for the specified all-thread rod.

5. Allow the Epoxy to Cure

Do not load the anchors or mount the light pole until the epoxy has reached the required cure time for the jobsite temperature.

Important Installation Note

The drill-and-epoxy method is intended to create new anchor locations in an existing concrete footing. These new anchors use fully threaded rod rather than traditional embedded J- or L-style anchor bolts. The existing footing, concrete condition, bolt circle, edge distance, embedment depth, pole specifications, and structural load requirements should all be evaluated before installation.

Light pole base with anchor bolts on concrete footing for engineering requirements

Technical & Engineering Requirements

The published AT.75 and AT1 load charts are based on specific installation conditions, footing characteristics, bolt-circle dimensions, and structural requirements. Projects that fall outside those conditions may require additional engineering before installation.

Published Engineering Conditions

  • Properly reinforced concrete
  • Minimum 4,000 PSI concrete
  • Minimum edge distance of 1-3/4″
Required embedment depth:
  • AT.75: 9″
  • AT1: 10″
  • Applicable published bolt-circle tables
  • Four-bolt square light pole applications

Project Conditions That Must Be Evaluated

  • Pole height and shaft size
  • Manufacturer-specified anchor-bolt diameter
  • Bolt circle
  • EPA / wind-load requirements
  • Existing footing condition
  • Concrete strength and reinforcement
  • Available edge distance
  • Whether the project falls within the published AT load charts

When Additional Engineering May Be Required

Additional engineering may be needed when the existing concrete is below 4,000 PSI, the bolt circle is smaller than the published range, the required loads exceed the published tables, footing conditions are unusual, or another project condition falls outside the standard AT.75 or AT1 engineering.

Which Anchor Bolt Kit Should I Use?

The correct kit depends on the light pole manufacturer’s anchor-bolt requirements, pole size, bolt circle, footing conditions, and structural load requirements. As a general guideline, AT.75 is used for applications requiring 3/4-inch anchor bolts, while AT1 is used where 1-inch anchor bolts are specified.

3/4-inch all-thread anchor bolt for AT.75 light pole retrofit kit
3/4"

ANCHOR BOLT

Choose AT.75 When

  • The pole manufacturer specifies 3/4-inch anchor bolts
  • The required bolt circle is 7 inches or larger
  • The project falls within the applicable AT.75 load chart
  • The existing footing can provide 9 inches minimum embedment
  • The required edge distance can be maintained

General application guidance: 3/4-inch anchor bolts are commonly used on poles up to approximately 4 inches in diameter and 25 feet in height, depending on the manufacturer and project loads.

1-inch all-thread anchor bolt for AT1 light pole retrofit kit
1"

ANCHOR BOLT

Choose AT1 When

  • The pole manufacturer specifies 1-inch anchor bolts
  • The required bolt circle is 9 inches or larger
  • The project falls within the applicable AT1 load chart
  • The existing footing can provide 10 inches minimum embedment
  • The required edge distance can be maintained

General application guidance: 1-inch anchor bolts are commonly used on poles approximately 5 inches in diameter and larger, up to around 40 feet in height, depending on the manufacturer and project loads.

Start With the Pole Manufacturer’s Requirements

Do not select AT.75 or AT1 based on pole height alone. Confirm the manufacturer-specified anchor-bolt diameter, bolt circle, EPA/load requirements, and footing conditions before choosing the kit.

Frequently Asked Questions About Light Pole Anchor Bolt Replacement

Light pole anchor bolt problems often appear when replacing an existing pole, installing a different pole on an existing footing, or dealing with damaged hardware.

Can light pole anchor bolts be replaced?

Traditional J- or L-style anchor bolts that are embedded in concrete generally cannot be simply removed and replaced. Replacing them typically requires installing a new concrete footing or removing and rebuilding a portion of the existing footing with new reinforcement and anchor bolts.

For qualifying applications, Light Pole Systems may instead recommend an Anchor Bolt Adapter or a drill-and-epoxy retrofit system using fully threaded rod.

Need additional information? Review our Light Pole Replacement Tools Guide for more information about equipment used during light pole replacement projects.

Related Light Pole Anchor Bolt Resources

Use these guides and product pages to compare repair options, verify bolt patterns, confirm anchor-bolt sizing, and learn more about installing new anchors in an existing concrete footing.

Anchor Bolt Adapter

When the existing anchor bolts are still structurally usable but the replacement light pole has a different bolt pattern, an Anchor Bolt Adapter may allow the existing footing and anchors to remain in place.

How to Install Anchor Bolts in Existing Concrete

Review the drill-and-epoxy process for creating new anchor locations in an existing concrete footing, including preparation, drilling, cleaning, epoxy installation, and threaded-rod placement.

How to Measure Light Pole Bolt Patterns

Learn how to measure light pole bolt-circle and bolt-square dimensions before selecting a replacement pole, Anchor Bolt Adapter, or drill-and-epoxy retrofit solution.

Light Pole Anchor Bolt Sizing

Review common light pole anchor-bolt sizes and the factors that affect anchor selection, including pole specifications, bolt diameter, and project requirements.

Need Help Choosing the Right Anchor Bolt Solution?

Every light pole replacement project is different. Light Pole Systems can help review the existing footing, anchor-bolt condition, required bolt circle, replacement pole specifications, and structural requirements to determine whether an Anchor Bolt Adapter, AT.75, AT1, or another solution should be evaluated.